Xtra Glo Fire Exit Arrow Down Signs

SKU
FE042LRPHX
£25.95
Free delivery on orders of £50
    •  Accept payments via PayPal
    •  Accept payments via credit card
    •  Over 20,000 products
    •  UK mainland delivery
    •  One page checkout
    •  FREE delivery on orders over £50

Xtra Glo Fire Exit Arrow Down Sign

An Xtra Glo Fire Exit Arrow Down Sign is an emergency fire escape type of navigation sign designed to glow very brightly in the dark and is used for showing people the fire exit door is below or by going down the stairs and conveys the message "Fire exit arrow down" which means the fire exit door is located blow or is by travelling down the stairs. In buildings where guiding the occupants in the straight on or straight ahead direction is required installing fire exit straight on signs which feature an arrow pointing in the up direction are ideal, where people in corridors are required to go down in the event of an evacuation installing fire exit down arrow signs are ideal as they are visible from both sides of the corridor, buy your Xtra Glo Fire Exit Arrow Down Signs on-line with SafetyBox.

To provide fire escape guidance in public buildings and public areas where virtually indestructible, impact resistant, vandal resistant which are under surface printed to protect the message is needed the polycarbonate material fire exit arrow down signs offer the ideal solution, made from polycarbonate it allows you to mount them above fire exit doors or in stairwells in urban and public areas to help resists damage. Building which have many fire exits to mark up and identify to the occupants will benefit from the packs of 6 arrow down fire exit signs which are perfect for showing the occupants the fire exit routes in multiple locations such as on each level of the stairs in stairwells and on each floor in high rise buildings.

Xtra Glo Fire Exit Arrow Down Sign Specifications

  • View the full range of fire exit arrow down signs
  • You may also be interested in the Fire Exit With Arrow Down Polycarbonate Signs
  • A similar choice are the Fire Exit Arrow Down 6 Pack Signs
    • Ensures compliance under the latest signs & signals regulations
    • Display area Indoor and Outdoor
    • Colour - Background Fluorescent Green
    • Colour - Text Fluorescent Yellow
    • Direction Down
    • Finish Environmentally friendly polyester film
    • Fixing Various - Available Separately
    • Material Rigid Plastic
    • Material Thickness 1.2 mm
    • Orientation Landscape
    • Photoluminescence Highly Photoluminescent
    • Shape Rectangle
    • Sign/Symbol Running man right
    • Arrow down
    • Sign Text/Symbol Symbol and Text
    • Sign Type Fire Exit
    • Size 150 x 450 mm
    • Ultra-high initial brightness
    • Illumination - 24hrs +
    • Recharge time - 5 minutes in normal lighting
    • PSPA Class C
    • Supplied in Single
    • Text Fire exit

    Guidance Regarding Escape Routes

    This information provides further guidance on the general principles that apply to escape routes and provides examples of typical escape route solutions for a range of common building layouts. The guidance is based on premises of normal risk so if your premises (or part of your premises) are higher (or lower) risk you should adapt the solution accordingly.

    Levels Of Risk

    In order to apply the guidance, you need to understand that in any fire situation, the time that people have to escape before they could become affected by the fire is limited. Providing them with sufficient time usually means that as well as having appropriate way of detecting and giving warning in case of fire, the distance that people have to travel to make their escape to a place of reasonable or total safety must be restricted.

    The travel distances which are usually appropriate for this purpose (and are suggested later in this section) vary according to the level of risk in the premises (or part of them). To check your escape routes will need to form a judgement about the level of risk that people may be at after you have taken other reduction (preventative and protective) measures.

    In premises where there is a likelihood of a fire starting and spreading quickly (or a fire could start and grow without being quickly detected and warning given) and affect the escape routes before people are able to use them, then the risk should normally be regarded at "higher". Such premises could include those where significant quantities of flammable materials are used or stored; ready sources of ignition are present, e.g. heat producing machinery and processes; premises where significant numbers of people present are likely to move slowly or be unable to move without assistance; and premises where the construction provides hidden voids or flues through which a fire could quickly spread.

    In premises where there is a low occupancy level and all the occupants are able bodied and capable of using the means of escape without assistance; very little chance of a fire; few if any highly combustible or flammable materials or other fuels for a fire; fire cannot spread quickly; and will be quickly detected so people will quickly know that a fire has occurred and can make their escape, then the risk can usually be regarded as "lower".

    In most cases however, the risk will usually be "normal". The travel distances suggested are not hard and fast rules and should be applied with a degree of flexibility according to the circumstances. For example, in premises where the risk might otherwise be considered "normal" but where there are a significant number of people who move slowly or may need assistance to evacuate, it would usually be appropriate to consider this a "higher risk". However, where other measures are in place to mitigate this, such as the availability of extra assistance and this has been planned for in your emergency plan, it may be that the risk level can be regarded as "normal to higher".

    Equally, in premises where the risk category would otherwise be "lower" but for the fact that a small number of occupants may move slowly or need assistance, it may be appropriate to categorise the risk as "normal" in these circumstances.

    Suitability of Escape Routes

    You should ensure that your escape routes are;

      • Suitable.
      • Easily, safely and immediately usable at all relevant times.
      • Adequate for the number of people likely to use them.
      • Free from any obstructions, slip or trip hazards;
      • Available for access by the emergency services.

      In multi-occupied premises, escape routes should normally be independent of other occupiers, i.e. people should not have to go through another occupier`s premises as the route may be secured or obstructed. Where this is not possible, then robust legal agreements should be in place to ensure their availability at all times.

      All doors on escape routes should open in the direction of escape and ideally be fitted with a safety vision panel. This is particularly important if more than 60 people use them or they provide an exit from an area of high fire risk.

      At least two exits should be provided if a room/area is to be occupied by more than 60 persons. This number of 60 can be varied in proportion to the risk; for a lower risk there can be a slight increase, for a higher risk, lower numbers of persons should be allowed.

      Movement of persons up or down a group of not less than three steps will be so obvious to those following that they will be prepared for the change in level, but movement up or down one step is not so readily observed and may easily lead to a fall. Wherever practical, differences of level in corridors, passages and lobbies should be overcome by the provision of inclines or ramps of gradients not exceeding 1 in 12 or steps not having less than three risers in any flight. Corridors and passages should be level for a distance of 1.5 metres in each direction from any steps.

      Any mirrors situated in escape routes should be sited so that persons escaping from a fire will not be thrown into confusion by any reflecting image of the route they are using, or be misled as to the direction they should take to reach fire exits. While not normally acceptable, the use of ladders, floor hatches, wall hatches or window exits may be suitable for small numbers of able-bodied, trained staff in exceptional circumstances.

More Information
Find By Price £25.95
Short Description